1 & 2 Hour Rated Fire Doors

  • Door and panel heights are variable to suit individual requirements.Fire Resistent Door Brisbane Qld

  • Doors and panels have square meeting edges, and require the normal 3mm maximum clearance demanded by the Australian Fire Door Code AS 1905, Part 1-1990.
  • Decorative trim such as timber or plastic moulding may be specified to one or both surfaces, and to your choice of patterns.

Maximum Available Sizes (mm)

  • Single Leaf: 3600 x 1500 x 48
  • Single Leaf: 2400 x 1118 x 38
  • Double Leaf: 3000 x 3000 x 48
  • Available with panel over transom to 4000mm overall.
  • Available with panel over (no transom) in single leaf to 3600mm overall.

Tested and Approved for use in:

  • Masonry walls.
  • Gypsum block walls.
  • Aerated concrete blocks.
  • Steel stud walls.
  • Hardie "Styrocon" panel walls.
  • lnsulboard panel walls.
Blue Fire Resestent Door
  • Plywood for paint
  • Selected veneer faced plywoood.
  • Sheet steel faces and edges.
  • Sheet aluminium.
  • 'Acrovyn' RV.C. facings.

Edge Details:

  • 10mm timber concealed or exposed.
  • 1mm veneer for decorative doors.
  • Steel channels or flats.
  • Aluminium anodized (available with smoke seals).
  • Laminate (Formica) to stiles.

Hardware Options:

To our knowledge, every lockset, surface mounted door closer and concealed closer designed for use with fire doorsets have been tested as compatible with Pyropanel® doorsets.

Special Hardware: such as

  • Panic bars.
  • Card-Key hotel locks.
Burnt Door
  • agnetic security locks.
  • Smoke seals for 'hot' and 'cold' smoke.
  • Kickplates of steel, 'Acrovyn' vinyl etc.
  • Vent grilles with automatic drop shutters.
  • Security bolts.
  • Sound and dust seals.
  • Vision panels with clear or wire cast glass
  • Aluminium faced shelf to form stable door.

Frame Profiles:

  • 1.1mm or 1.5mm thickness Zincanneal steel.
  • Timber door frames to detail.

Weight (Plywood faced):

  • 48mm - 22kg/in2
  • 38mm - 19kg/in2
Fire Door

Meeting Edge Options

  • Standard aluminium J-section to each leaf,
    in conjunction with stainless steel chain bolt or Pyropanel® Roller Latch or concealed UDM
  • Autobolt, to non-active leaf, and sequence closing device.
  • Rebated aluminium clad meeting stiles.
  • Bull-nose with 'Pyroseal' smoke seals (up to 3 hour rated).
  • Square meeting stiles (1 hour rated only).

2 Hour Rated Fire Doors

Right is a test carried out on our 2hr doors. 

  • Maximum Available Sizes (mm)
  • Single Leaf: 3000 x 1500 x 48
  • Single Leaf: 2340 x 1020 x 38
  • Double Leaf: 3000 x 3000 x 48
Available with panel over transom to 3600mm overall.

Tested and Approved for use in:

  • Masonry walls.
  • Gypsum block walls.
  • Timber stud walls.
  • Steel stud walls.
  • Hardie "Styrocon" walls.

Your choice of facings:

  • Plywood for paint.
  • Selected veneer faced plywood.
  • Fire retardant grade laminate.
  • Sheet steel faces and edges.
  • Sheet aluminium.
  • 'Acrovyn' P.V.C. facings.

Edge Details:

  • 10mm timber concealed or exposed.
  • 1mm veneer for decorative doors.
  • Steel channels or flats.
  • Aluminium anodized (available with smoke seals).
  • Laminate (Formica) to stiles.

Hardware Options:

To our knowledge, every lockset, surface mounted door closer and concealed closer designed for use with fire doorsets have been tested as compatible with Pyropanel~ doorsets.

Special Hardware:

  • Panic bars.
  • Card - Key hotel locks.
  • Electrically operated strikers.
  • Magnetic security locks.
  • Smoke seals for 'hot' and 'cold' smoke.
  • Kickplates of steel, 'Acrovyn' vinyl etc.
  • Vent grilles with automatic drop shutters.
  • Security bolts.
  • Sound and dust seals.
  • Vision panels with clear or wire cast glass.
  • Aluminium faced shelf to form stable door.

Frame Profiles:

  • 1.2mm or 1.5mm thickness Zincanneal steel. Composite (timber veneered) door frames to detail.
  • Weight (Plywood faced):
  • 48mm - 22kg/in2
  • 38mm - 19kg/rn2

Usage:

Where specified or legislated to provide 2HR protection of openings in stairways, plant rooms, substations etc.